UPS is a new generation power supply designed for power plants and substations. It has on-line and zero-delay conversion function. It is mainly used in places with high voltage requirements such as power remote control, RTU, DCS system, power carrier , Monitoring and so on.
1. Luxury cabinets, nice
2, the city power supply / DC inverter power supply between the zero-delay conversion; inverter bypass ≤ 4ms
3, AC input, DC input and AC uninterrupted output is completely isolated
4, the use of DSP digital control technology, intelligent detection and monitoring functions
5, high-speed IGBT drive inverter
6, passive contacts and RS232 / 485 monitoring
7, with overvoltage, undervoltage, overcurrent, short circuit and other protection
8, large-screen LCD Chinese operation monitoring interface.
Type |
BUS- 33010 |
BUS- 33015 |
BUS- 33020 |
BUS- 33030 |
BUS- 33045 |
BUS- 33075 |
BUS- 33100 |
BUS- 33200 |
|||
Input |
AC voltage(V) |
380V±35% |
|||||||||
DC voltage(V) |
DC360V |
||||||||||
Frequency(Hz) |
45~65Hz |
||||||||||
Power factor |
0.8 |
||||||||||
Output |
Rated Capacity(KVA) |
10 |
15 |
20 |
30 |
45 |
75 |
100 |
200 |
||
Output rated voltage and frequency |
380Vac , 50Hz |
||||||||||
Output voltage accuracy(V) |
380 ± 1% |
||||||||||
Output frequency accuracy(Hz) |
50 ± 0.05 |
||||||||||
Waveform distortion(THD) |
≤ 3% |
||||||||||
Dynamic Response(load 0-100%) |
5% |
||||||||||
Overload capability |
150%,10s |
||||||||||
Peak factor(CF) |
3:1 |
||||||||||
Inverter efficiency(80% Resistive load) |
90% |
||||||||||
Conversion Time(ms) |
Electricity → ←battery |
0 |
|||||||||
Inverter→←bypass |
≤ 4ms |
||||||||||
Work environment |
Noise(1meter) |
≤ 50dB |
|||||||||
Ambient temperature |
-10℃ ~+ 50 ℃ |
||||||||||
Humidity |
0~90%,Non-condensing |
||||||||||
Mechanical Dimensions (W * D * H)mm |
600*800*1000 |
650*900*1200 |
700*1200*1600 |
||||||||
Protection |
Enter reversed protection, input under-voltage protection, output overload protection, output short-circuit protection, overheat protection. |